E/LNE - Series
Suitable for firetube, firebox and watertube boilers; the E series features a low pressure drop head design and low motor horsepower requirements for increased efficiencies. The E series offers natural gas, propane gas, air atomized #2 oil and combination gas/oil fuel options at capacities from 8,400,000 to 42,000,000 Btu/hour. Incorporating advanced technology, the E series offers low NOx emissions, and up to 10:1 turndown on natural gas and 8:1 turndown on light oil.
|
Capacities and Specifications
| Burner Size |
84 | 105 | 126 | 147 | 168 | 210 | 252 | 294 | 336 | 378 | 420 |
| Frame Size |
1 | 1 | 1 | 1 | 2 | 2 | 2 | 3 | 3 | 3 | 3 |
| Gas Input (Mbtu/hr) |
8,400 | 10,500 | 12,600 | 14,700 | 16,800 | 21,000 | 25,200 | 29,400 | 33,600 | 37,800 | 42,000 |
| Oil Input (U.S. gph) |
60.0 | 75.0 | 90.0 | 150.0 | 120.0 | 150.0 | 180.0 | 210.0 | 240.0 | 270.0 | 300.0 |
| Boiler Horsepower |
200 | 250 | 300 | 350 | 400 | 500 | 600 | 700 | 800 | 900 | 1,000 |
| Blower Motor Horsepower |
3 | 5 | 5 | 7.5 | 10 | 15 | 15 | 20 | 20 | 25 | 30 |
| Separate Compressor Motor HP |
3 | 3 | 3 | 5 | 5 | 5 | 7.5 | 7.5 | 7.5 | 15 | 15 |
| Oil Metering System Motor HP |
1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 1 |
| Furnace Pressure("W.C) |
4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 |
| Standard Gas Train Pipe Size (in.) |
2.5 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 4.0 |
| Gas Pressure Required (PSI) |
2.1 | 2.2 | 2.5 | 2.7 | 3.0 | 3.9 | 4.3 | 2.6 | 3.1 | 3.6 | 3.7 |
| Shipping Weight (lbs) |
1,500 | 1,500 | 1,500 | 1,500 | 2,200 | 2,200 | 2,200 | 5,000 | 5,000 | 5,000 | 5,000 |
| Burner Size |
84 | 105 | 126 | 147 | 168 | 210 | 252 | 294 | 336 | 378 | 420 |
| Frame Size |
1 | 1 | 1 | 1 | 2 | 2 | 2 | 3 | 3 | 3 | 3 |
| Gas Input (Mbtu/hr) |
8,400 | 10,500 | 12,600 | 14,700 | 16,800 | 21,000 | 25,200 | 29,400 | 33,600 | 37,800 | 42,000 |
| Oil Input (U.S. gph) |
60.0 | 75.0 | 90.0 | 150.0 | 120.0 | 150.0 | 180.0 | 210.0 | 240.0 | 270.0 | 300.0 |
| Boiler Horsepower |
200 | 250 | 300 | 350 | 400 | 500 | 600 | 700 | 800 | 900 | 1,000 |
| Blower Motor Horsepower |
5 | 5 | 7.5 | 10 | 15 | 20 | 25 | 25 | 30 | 40 | 50 |
| Separate Compressor Motor HP |
3 | 3 | 3 | 5 | 5 | 5 | 7.5 | 7.5 | 7.5 | 15 | 15 |
| Oil Metering System Motor HP |
1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 3/4 | 3/4 | 3/4 | 3/4 | 1 | 1 |
| Furnace Pressure("W.C) |
4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 |
| Standard Gas Train Pipe Size (in.) |
2.5 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 4.0 |
| Gas Pressure Required (PSI) |
2.1 | 2.2 | 2.5 | 2.7 | 3.0 | 3.9 | 4.3 | 2.6 | 3.1 | 3.6 | 3.7 |
| FGR Line Piping Size (in.) |
6.0 | 6.0 | 6.0 | 6.0 | 8.0 | 8.0 | 8.0 | 10.0 | 10.0 | 10.0 | 10.0 |
| Shipping Weight (lbs) |
2,000 | 2,000 | 2,000 | 2,000 | 3,000 | 3,000 | 3,000 | 5,500 | 5,500 | 5,500 | 5,500 |
|