E-Series
Suitable for firetube, firebox and watertube boilers; the E/series features a low pressure drop head design and low motor horsepower requirements for increased efficiencies. Incorporating advanced technology, the E/series offers low NOx emissions, and up to 10:1 turndown on natural gas and 8:1 turndown on light oil.
|
| | |
|
Features Include:
- Gas and light oil fuels
- Standard and low Nox capabilities
- Up to 10:1 turndown on natural gas, 8:1 turndown on light oil
- Advanced control options include Parallel Positioning, O2 trim, variable speed drives and more
- Low motor horsepower for increased energy efficiency
- Hinged combustion head for easy access and maintenance
- U.L. Listed through model E-252 including many advanced control options
|

|
| | |
Capacities and Specifications
| Burner Size |
84 | 105 |
126 | 147 |
| Gas Input(MBtu/hr) |
8,400 | 10,500 | 12,600 | 14,700 |
| Oil Input(U.S. gph) |
60.0 | 75.0 | 95.0 | 150.0 |
| Boiler Horsepower |
200 | 250 | 300 | 350 |
| Blower Motor Horsepower |
3 | 5 | 5 | 7.5 |
| Furnace Pressure("W.C) |
3 | 3 | 3 | 3 |
| Burner Size |
168 | 210 |
252 |
| Gas Input(MBtu/hr) |
16,800 | 21,000 | 25,200 |
| Oil Input(U.S. gph) |
120.0 | 150.0 | 180.0 |
| Boiler Horsepower |
400 | 500 | 600 |
| Blower Motor Horsepower |
10 | 15 | 15 |
| Furnace Pressure("W.C) |
5 | 5 | 5 |
| Burner Size |
294 | 336 |
378 | 420 |
| Gas Input(MBtu/hr) |
29,400 | 33,600 | 37,800 | 42,000 |
| Oil Input(U.S. gph) |
210.0 | 240.0 | 270.0 | 300.0 |
| Boiler Horsepower |
700 | 800 | 900 | 1000 |
| Blower Motor Horsepower |
15 | 20 | 20 | 25 |
| Furnace Pressure("W.C) |
6 | 6 | 6 | 6 |
| Burner Size |
504 | 630 |
| Gas Input(MBtu/hr) |
50,400 | 63,000 |
| Oil Input(U.S. gph) |
360.0 | 450.0 |
| Boiler Horsepower |
1200 | 1500 |
| Blower Motor Horsepower |
40 | 75 |
| Furnace Pressure("W.C) |
8 | 8 |
|
| | |
Notes (E-Series):
- Firing rates based on 60 cycle and altitudes to 2000 feet above sea level.
For blower wheel and motor sizes at higher altitudes, and 50 cycle applications,
consult factory.
- Oil input based on No. 2 oil @ 140,000 Btu/gal.
- Gas input based on Natural Gas @ 1,000 Btu/cu.ft. and 0.60 specific gravity.
- Lower furnace pressures may reduce motor HP requirements